原装进口CIRCUTOR(西谷铎)固定式电能质量分析仪CVM A系列西班牙生产
原装进口CIRCUTOR(西谷铎)固定式电能质量分析仪CVM A系列西班牙生产
产品价格:¥99999999999(人民币)
  • 规格:CVM A1500
  • 发货地:巴塞罗那
  • 品牌:
  • 最小起订量:1台
  • 诚信商家
    会员级别:钻石会员
    认证类型:未认证
    企业证件:未通过
    认证信息:未认证

    商铺名称:CIRCUTOR(西谷铎) 驻大中华区办事处

    联系人:(小姐)

    联系手机:

    固定电话:

    企业邮箱:shanghai@circutor.com

    联系地址:南京西路1308号1606室

    邮编:200041

    联系我时,请说是在五金机电网上看到的,谢谢!

    商品详情

      项目询价 及 相关授权经销商查询,请联系:

      电话:021-52287226(直线)

      邮箱:shanghai@circutor.com

      中国大陆及港澳台地区,现由CIRCUTOR(西谷铎)大中华区办事处: CIRCUTOR(西谷铎)Shanghai上海统一负责管理



      CVM-A1500A-ITF-485-ICT2


      CVM-A1500A-ITF-485-ICT2, Power quality analyzers with recording of quality events and transients Calibration Certificate (IEC 61000-4-30 Ed.2) Class A

      Code: M563110000A00

      •  Protocol: Modbus/RTU | BACnet | webserver (HTTP) | XML | HTML5
      •  Memory: 200 MB
      •  Memory: Yes
      •  Events / Waveform: Yes
      •  Certification: IEC 61000-4-30 (Class A)
      •  Energy accuracy: 0,2S (.../5A)
      •  Communications: RS-485 | Ethernet
      •  Transistor output: 2
      •  No relays: 2
      •  Digital inputs: 2
      •  Harmonics: 63
      •  Input current: .../5 A | .../1 A | 250 mA
      •  Mounting: Pannel
      •  Modules: 144 x 144

      DESCRIPTION

      CVM-A1500 is a panel mounted power quality analyzer with EMS (Energy Management Software) integrated. Its internal Web Server (html5) allows any user to have full installation control by using any web browser.

      Designed to be installed in the most relevant or critical part of electric installations since it registers and monitors a wide range of variables (almost one year of data with RMS, maximum and minimum values). The device also registers power quality events such as swells, dips, interruptions (every half cycle) and transients (according to IEC 61000-4-30 Class A). Any event will be immediately captured with the voltage and current waveform.

      This model adds the measurement of power quality variables (defined in the standard EN 50160) such as flicker, unbalance (Kd) and asymmetry (Ka) coefficients or voltage and current harmonics decomposition up to 63th.  In addition it is possible to monitor in real time the instantaneous waveforms of voltage and current through its oscilloscope function.

      As an added value, CVM-A1500 displays the number of events and transients on each affected phase with the level reached, duration and its associated waveform. In addition, those events are directly displayed in CBEMA, ITIC y SEMI-F47 graphs.

      The smart design of the CVM-A1500 allows users to customize their own screens in order to access to the information faster and easy. Remark that the device allows the connection though PowerStudio software to save and store, in a redundant way, all the information in a server or PC avoiding memory limits.

      • Dimensions:144 x 144 mm
      • Energy Management Software (EMS) included with historical data register
      • Register of power quality events, waveforms and instantaneous parameters.
      • Expandable up to 3 modules (inputs/outputs and communications)
      • VGA color display with high definition
      • IP 65 with airtight seal
      • 5 voltage channels + 4 ITF current channels
      • Active energy class 0,2S (IEC 62053-22)
      • Universal switching power supply AC/DC or DC
      • Ethernet communications (Web Server) + RS-485 (ModBus RTU or BACnet protocol)
      • 5 user customizable screens
      • 3 tariffs (selectable by digital input or by communications)
      • Cost calculation(any currency) and emissions of kgCO2
      • 2 relay outputs for alarms + 2 transistor outputs for alarms or pulses + 2 digital inputs to select tariff, to control logical states or pulse centralizer from any external meter.
      APPLICATIONS
      • Control, monitoring and logging of the power quality in High and Low Voltage distribution panels. Performed directly or remotely thanks to its WEB server. Integration in SCADA systems through XML requests.
      • 4 alarms (2 per transistor and 2 per relay), fully and independently programmable according to a low or high value, hysteresis, connection/disconnection delays, normally open or closed standby status and interlocking.
      • Generation of impulses with transistor outputs, fully and independently configurable over any incremental parameter (energy, costs, kgCO2, total meter or tariff hours).
      • Transducer converting analogue signals to any instantaneous parameter measured or calculated by the unit, with built-in expansion modules with analogue outputs.
      • Display of process signals featuring a built-in expansion module with analogue inputs, with optional reporting of these signals to SCADA systems through communications systems.
      • Control of electrical load or alarm signal operations by programming the transistor or relay outputs that are built-in or added through expansion modules.
      • Datalogger integrated with Web server and XML (log of historical data).

      SPECIFICATIONS

      AC POWER SUPPLY
      Installation category
      CAT III 300 V
      Consumption
      máx. 29.4 VA
      Frequency
      45 ... 65Hz
      Nominal voltage
      100…240 V ~
      DC POWER SUPPLY
      Installation category
      CAT III 300 V
      Consumption
      max. 11.9 W
      Nominal voltage
      120 … 300 Vdc
      MECHANICAL CHARACTERISTICS
      Size (mm) width x height x depth
      144.7 x 144.7 x 131.1 (mm)
      Envelope
      Self-extinguishing UL94-V0 plastic
      Fastening
      Pannel (DIN43700) 138x138
      Weight (kg)
      0,95
      ENVIRONMENTAL CHARACTERISTICS
      Protection class
      IP 40 (Front), IP 65 (Sealing), IP 30 (unmounted)
      Relative humidity (without condensation)
      5 ... 95%
      Storage temperature
      -20… +80 oC
      Operating temperature
      -10…+50 oC
      STANDARDS
      Certifications
      UL/CSA 61010-1 3rd edition
      Electrical safety, Maximum height (m)
      2000
      Standards
      UNE EN 61010, UNE EN 61000-6-4, UNE EN 61000-6-2, IEC 664, UNE-EN 55022, Measures according to : IEC 61557-12
      CURRENT MEASUREMENT CIRCUIT
      Installation category
      CAT III 600 V
      Nominal current (In)
      …/5A, …/1A, …/0.250A
      Phase current measuring range
      0.01…10A (…/5A),0.01…2A (…/1A), 0.01…0.5A (…/0.250A)
      Neutral current measuring range
      0.02...0.5A (.../0.250A, calculated)
      Maximum input current consumption
      0,9 VA
      Maximum pulse current
      100 A
      Minimum current measurement
      0,01 A (…/5A, …/1A, …/0,250A
      VOLTAGE MEASUREMENT CIRCUIT
      Installation category
      CAT III 600V
      Input impedance
      1.2MΩ
      Frequency measuring range
      40…70 Hz
      Voltage measuring range
      20…600 V~
      Maximum input voltage consumption
      0,15 VA
      Minimum measurement voltage (Vstart)
      10 V~
      COMMUNICATIONS
      Fieldbus (BACnet)
      MS/TP
      Fieldbus (ModBus)
      RS-485 / RTU
      Stop bits (BACnet)
      1
      Stop bits (ModBus)
      1-2
      Parity (BACnet)
      non
      Parity
      non-pair-impar (Modbus)
      Protocol
      ModBus/BACnet
      Speed
      9600-19200-38400-57600-76800-115200
      USER INTERFACE
      LED
      3 LED
      Resolution of the display
      VGA (640x480)
      Keyboard
      Capacitive, 3 keys
      Display type
      TFT color
      DIGITAL INPUTS
      Input/output insulation
      4 kV
      Quantity
      3
      Type
      Potential-free contact
      Maximum short-circuit current
      5 mA
      Maximum open circuit voltage
      15 Vdc
      DIGITAL RELAY OUTPUTS
      Electrical life (at maximum load)
      3x104 cycles
      Mechanical life
      1x107 cycles
      Maximum switching capacity
      1500 VA
      DIGITAL TRANSISTOR OUTPUTS
      Pulse width
      1 ms
      Quantity
      2
      Pulse output, time period (Ton / Toff)
      0,3 ms/0,7 ms
      Maximum frequency
      1 kHz
      Maximum current
      130mA
      Maximum voltage
      48 Vdc
      MEASUREMENT ACCURACY
      Current asymmetry (Ka)
      class A (IEC 61000-4-30)
      Voltage asymmetry (Ka)
      Class A (IEC 61000-4-30)
      Current unbalance (Kd)
      class A (IEC 61000-4-30)
      Voltage unbalance (Kd)
      class A (IEC 61000-4-30)
      Frequency measurement
      Class 0.02 (…/5A, …/1A, …/0.250A)
      Phase current measurement
      Class 0.2 ±1 digit 0.05…8A (…/5A),0.01…1.2A (…/1A),0.01…0.3A (…/0.250A)
      Neutral current measurement
      class 1 ±1 digit 0.05…6A (…/5A),0.01…1.2A ( …/1A), calculated (…/0.250A)
      Reactive energy measurement (kvarh)
      (IEC 62053-23) Class 1 (…/5A), Class 2 (…/1A, …/0.250A)
      Reactive power measurement (kvar)
      (Vn 230/110 Vac) Class 1 ±1 digit 0.05…6A (…/5A),0.01…1.2A ( …/1A), 0.01…0.3A (…/0.250A)
      Apparent power measurement (kVA)
      (Vn 230/110 Vac) class 0.5 ±1 digit 0.05…6A (…/5A),0.01…1.2A ( …/1A), 0.01…0.3A (…/0.250A)
      Active energy measurement (kWh)
      (IEC 62053-22) Class 0.2S (…/5A), Class 0.5S (…/1A), Class 0.5S (…/0.250A)
      Power factor measurement
      class 0,5 (…/5A, …/1A, …/0.250A)
      Current THD
      class 1 (…/5A, …/1A, …/0.250A)
      Voltage THD
      class 1 (…/5A, …/1A, …/0.250A)
      Phase voltage measurement
      class 0.2 ±1 digit (20…600 Vca, …/5A, …/1A, …/0.250A)
      Neutral voltage measurement
      Class 0.5 ±1 digit (50…600 Vca, …/5A, …/1A, …/0.250A)
      Pinst. Flicker
      3 % (IEC 61000-4-15)
      Pst Flicker
      5 % (0,2…10 Pst) (IEC 61000-4-15)
      Current harmonics (THD)
      class 1 (…/5A, …/1A, …/0.250A)
      Voltage harmonics (THD)
      class 1 (…/5A, …/1A, …/0.250A)




    在线询盘/留言
  • 0571-87774297